北仑电厂机组失步保护RXZK动作行为的分析
引用本文:陈建民,聂宇本,张启达. 北仑电厂机组失步保护RXZK动作行为的分析[J]. 华东电力, 2004, 32(3): 34-36
作者姓名:陈建民  聂宇本  张启达
作者单位:华东电力调度通信中心,上海,200002;北仑发电厂,浙江,宁波,315208
摘    要:分析了北仑电厂高压母线侧相间故障引起发电机失步保护误动的动作原因,并介绍了解决问题的方法。指出应充分考虑系统故障对发电机异常运行保护测量判据的影响,防止其误动。

关 键 词:继电保护  发电机  失步
文章编号:1001-9529(2004)03-0034-03
修稿时间:2003-09-25

Analysis of actional behavior of loss of synchronism protection RXZK in Beilun Power Plant
CHEN Jian-min,NIE Yu-ben,ZHANG Qi-da. Analysis of actional behavior of loss of synchronism protection RXZK in Beilun Power Plant[J]. East China Electric Power, 2004, 32(3): 34-36
Authors:CHEN Jian-min  NIE Yu-ben  ZHANG Qi-da
Affiliation:CHEN Jian-min~1,NIE Yu-ben~1,ZHANG Qi-da~2
Abstract:The cause of loss of synchronism protection RXZK malfunction when a phase to phase fault took place on the HV busbar in Beilun Power Plant was analyzed. The method to solve the problem was given. It was pointed out that the effect of system faults on the measurement criteria of the protection of the generator during abnormal condition should be fully considered to avoid malfunction of the protection.
Keywords:relay protection  generator  loss of synchronism