首页 | 本学科首页   官方微博 | 高级检索  
     

某办公楼空调系统故障分析及调试
引用本文:赵勇,罗万象.某办公楼空调系统故障分析及调试[J].暖通空调,2000,30(4):81-82.
作者姓名:赵勇  罗万象
作者单位:中国纺织工业设计院
摘    要:针对某办公楼出现的室内相对湿度过高、新风量不足、空气有异味等问题,分析了设计资料进行现场调研,采取降低冷水机组供回水温度、调节风机盘管风速、适当关闭风机盘管台数、清洗在等措施,基本解决了室内空气品质问题。探讨了该工程空调系统设计中不足之处和运行管理中应注意的问题。

关 键 词:办公楼  室内空气品质  风机盘管  新风  空调系统
修稿时间:1999-10-10

Trouble shooting and adjusting for the air conditioning system in an office building
Zhao Yong,Luo Wanxiang.Trouble shooting and adjusting for the air conditioning system in an office building[J].Journal Heating Ventilating and Airconditioning,2000,30(4):81-82.
Authors:Zhao Yong  Luo Wanxiang
Affiliation:By Zhao Yong and Luo Wanxiang
Abstract:Aims at the problems such as over high relative humidity, fresh air shortage and poor indoor air quality existed in an office building, analyses the design data and investigates in site. By reducing supply/return water temperatures of the water cooled chiller unit, regulating the air velocity from the fan coil unit, stopping some fan coil units properly and cleaning the air filter, largely solves these problems. Discusses the deficiencies in design and operation of the air conditioning system in the building.
Keywords:office building  indoor air quality  fan coil unit  fresh air