220kV电容式电压互感器的隐患事故分析
引用本文:吕丹,李电.220kV电容式电压互感器的隐患事故分析[J].电力电容器与无功补偿,2006(3).
作者姓名:吕丹  李电
作者单位:绍兴电力局,浙江,绍兴,31200;绍兴电力局,浙江,绍兴,31200
摘    要:通过现场测试,发现电容式电压互感器的电容量误差在国家标准之内,但电容量异常增加,且三相线电压明显不平衡,经进一步试验分析,判定电容器内部串联电容已部分击穿,提出了电容式压变运行及测试相应注意事项。

关 键 词:电容式电压互感器  电容量  异常

Analysis of 220kV Capacitor Voltage Transformer's Hidden Fault
LV Dan,LI Dian.Analysis of 220kV Capacitor Voltage Transformer's Hidden Fault[J].Power Capacitor $ Reactive Power Compensation,2006(3).
Authors:LV Dan  LI Dian
Abstract:Based on the practical tests,It is found that the CVT's capacitance increases abnormally,and the three phase voltages are obviously imbalanced,although the error of CVT′s capacitance is within the requirement specified by the national standard.Through further examination,it can be concluded that the inner in-series capacitors have been partly broken down.The attentions on CVT′s operation and testing are proposed.
Keywords:Capacitor voltage transformer(CVT)  Capacitance  Abnormality