不同充液率平板热管性能实验
引用本文:王岗,赵耀华,全贞花,王宏燕.不同充液率平板热管性能实验[J].化工进展,2019,38(5):2123-2131.
作者姓名:王岗  赵耀华  全贞花  王宏燕
作者单位:北京工业大学绿色建筑环境与节能技术北京市重点实验室,北京,100124;北京工业大学绿色建筑环境与节能技术北京市重点实验室,北京,100124;北京工业大学绿色建筑环境与节能技术北京市重点实验室,北京,100124;北京工业大学绿色建筑环境与节能技术北京市重点实验室,北京,100124
基金项目:国家自然科学基金(51778010)
摘    要:搭建了平板热管测试实验台,对不同充液率下热管性能进行了实验研究,并以最佳充液率的热管为研究对象,分析了加热功率、冷却水温及冷却水流速对热管性能的影响。实验结果表明:充液率为20%和30%时热管在各加热功率下展现了良好的性能,最小热阻为0.18℃/W和0.19℃/W,热导率为8158W/(m·℃)和8540W/(m·℃)。由于沸腾换热滞后性,相较于功率增加,功率减少时热管性能更优,同等加热功率条件下蒸发段温度更低。功率增加和功率减少对热管蒸发段热阻影响较大,而冷凝段热阻几乎不受影响。当冷却水温为17℃和22℃时,热管蒸发段温度比冷却水温为7℃和12℃时蒸发段温度低2℃左右。相较于冷却水温22℃时,冷却水温为17℃时热管蒸发段温度能更快达到稳定值。冷却水流速影响蒸发段温度及达到稳定运行的时间,实验表明热管工作的最佳冷却水流速为5.81g/s。

关 键 词:平板热管  微通道  相变  传热  热阻  热导率
收稿时间:2018-07-22

Characteristic of flat plate heat pipe with different filling ratios
Gang WANG,Yaohua ZHAO,Zhenhua QUAN,Hongyan WANG.Characteristic of flat plate heat pipe with different filling ratios[J].Chemical Industry and Engineering Progress,2019,38(5):2123-2131.
Authors:Gang WANG  Yaohua ZHAO  Zhenhua QUAN  Hongyan WANG
Affiliation:Beijing Key Laboratory of Green Built Environment and Energy Efficient Technology, Beijing University of Chemical Technology, Beijing 100124, China
Abstract:A test bed on flat plate heat pipe was built in order to study heat pipe performance with different filling ratios. Then the heat pipe with the best filling ratio was taken into account as the research object, the influences of increasing heating power, decreasing heat power, cooling water temperature and mass flow rate on heat pipe performance were analyzed. The results showed that heat pipe with filling ratio of 20% and 30% presented a good performance. The minimum thermal resistance was 0.18℃/W and 0.19℃/W, with the maximum effective thermal conductivity of 8158W/(m·℃) and 8540W/(m·℃), respectively. Compared to heat pipe performance with the increase heating power, the performance with the decrease heating power was better because of boiling hysteresis phenomenon, and evaporation section temperature was lower at the same heating power. The effect on thermal resistance of evaporation section was great with increasing and decreasing heating power, but the thermal resistance of condensation section was almost unaffected. The heat pipe evaporation section temperature with cooling water temperature of 17℃ and 22℃ was about 2℃ lower than that with cooling water temperature of 7℃ and 12℃. Compared to cooling water temperature of 22℃, evaporation temperature of heat pipe reached a stable value more quickly when cooling water temperature was 17℃. Thus, the heat pipe performance was best when cooling water temperature was 17℃. Synthesizes evaporation temperature, the time achieving a stable and water pump power consumption, the best mass flow rate for heat pipe was 5.81g/s.
Keywords:flat plate heat pipe  micro channels  phase change  heat transfer  thermal resistance  thermal conductivity  
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《化工进展》浏览原始摘要信息
点击此处可从《化工进展》下载全文