An experimental study on the thermal and fouling characteristics in a washable shell and helically coiled heat exchanger by the Wilson plot method
Authors:Koo  Kyoungmin  Hwang  Junhyeon  Hur  Hyun  Lee  Jaekeun  Na  Byungchul  Hwang  Yoonjae  Kim  Byungsoon  Ahn  Youngchull
Affiliation:1.School of Mechanical Engineering, Pusan National University, Busan, 609-735, Korea
;2.Air Conditioning & Energy Division, LG Electronics, Changwon City, Gyeongnam, 641-711, Korea
;3.EcoEnergy Research Institute, Busan, 609-735, Korea
;4.Department of Architectural Engineering, Pusan National University, Busan, 609-735, Korea
;
Abstract:

Brazed plate heat exchangers (BPHEX) are broadly used in water source heat pump systems for their large heat transfer capacity. Despite their high heat transfer rate, their high-performance rate tends to decrease sharply, due to fouling and they cannot be cleaned. So the thermal and fouling resistances of washable Shell and helically coiled tube heat exchangers (SCHEX) are designed and experimentally investigated in this study. Heat exchangers with two different tube types are studied and compared with a brazed plate heat exchanger. The overall thermal resistance coefficient of the heat exchangers as determined by using Wilson plots is 38% lower than that of the brazed plate heat exchanger at a Reynolds number of 2460. Fouling test results revealed that regular maintenance and physical cleaning can be used to maintain the thermal resistance of fouling of the washable heat exchanger at a level equal to or less than that of the brazed plate heat exchanger.