首页 | 本学科首页   官方微博 | 高级检索  
     

现场不拆引线测试500 kV氧化锌避雷器电气参数
引用本文:许红军. 现场不拆引线测试500 kV氧化锌避雷器电气参数[J]. 供用电, 2009, 26(5): 59-60
作者姓名:许红军
作者单位:大唐淮北发电厂电气检修公司,安徽,淮北,235000
摘    要:运行中的氧化锌避雷器要定期进行电气性能测试。介绍了直流1mA动作电压U1mA和0.75U1mA电压下的泄漏电流参数测试的拆高压引线与不拆高压引线两种测试方法、接线,以及实测结果的比较。分析和实测都表明,不拆高压引线测试方法可行,效果良好。

关 键 词:氧化锌避雷器  临界动作电压  泄漏电流

On-site Electric Parameter Measurement of 500kV Zinc Oxide Arrester without HV Lead Dismantled
XU Hongjun. On-site Electric Parameter Measurement of 500kV Zinc Oxide Arrester without HV Lead Dismantled[J]. Distribution & Utilization, 2009, 26(5): 59-60
Authors:XU Hongjun
Affiliation:XU Hongjun (Huaibei Datang Electric Power Plant Maintenance Company, Huaibei 235000,Anhui China)
Abstract:Zinc oxide arrester in operation stage needs electrical test periodically. The paper introduces two methods of measuring operating voltage U1mA and leakage current at voltage of 0.75 U1mA with or without HV lead of arrester dismantled, corresponding connections and the comparison of measured results. Both analysis and practical measurement show that the method without HV lead dismantled is flexible and well effective.
Keywords:zinc oxide arrester  critical operating voltage  leakage current