首页 | 本学科首页   官方微博 | 高级检索  
     

220kV计量电压互感器的现场测试及分析
引用本文:邵红雁. 220kV计量电压互感器的现场测试及分析[J]. 安徽电力, 2006, 23(1): 15-17
作者姓名:邵红雁
作者单位:安徽省电力科学研究院 安徽合肥230022
摘    要:电压互感器的误差与其二次负荷是直接关联的,现场测试应在电压互感器的运行电压以及实际二次负荷下进行。文中针对由于电压互感器实际的二次负荷与检验规定值(25%~100%)额定负荷相差较大,以致使运行电压互感器误差超差的原因进行了分析和讨论,提出了解决方法。

关 键 词:电压互感器  电能计量  误差

Site test and analysis of 220 kV metrical voltage transformer
Shao Hongyan. Site test and analysis of 220 kV metrical voltage transformer[J]. Anhui Electric Power, 2006, 23(1): 15-17
Authors:Shao Hongyan
Affiliation:Shao Hongyan
Abstract:Error of voltage transformer is directly associated with its secondary load, the site test must be conducted under working voltage and actual secondary load. This article analyzes and discusses the cause of error overrun of the 220 kV voltage transformer in operation in view of largish difference between the actual secondary load and specified probative 25%~100% rated load and puts forward a solution.
Keywords:voltage transformer  electric energy measurement  error