首页 | 本学科首页   官方微博 | 高级检索  
     


Active power variation in wind farms by varying the number of wind turbine units
Authors:S. T. Nagarajan  Narendra Kumar
Affiliation:1. Electrical Engineering Department, Delhi Technological University, Bawana Road, Delhi, Indiaselukka@yahoo.com;3. Electrical Engineering Department, Delhi Technological University, Bawana Road, Delhi, India
Abstract:Aggregated representation of wind turbine units in the wind farm has been normally adopted for modelling and analysis of dynamic performance, with power variation obtained by change of wind speed in the literature. This paper presents a different scenario of power variation of wind farms by the addition and removal of turbines in wind farms and its implication in modelling and stability of wind farms. The steady-state and dynamic stability with the aggregated model of the wind farm has been analysed with variation in the number of turbine units and has been corroborated with time domain simulation in DIgSILENT Power Factory software. It has been concluded that the variation in the number of wind turbines generators connected to the same transmission line has a minimal impact on the stability in nonseries-compensated line; however, significant impact on the stability has been observed in series-compensated system.
Keywords:induction generator  wind farm  stability  series compensation