Effect of tip clearance on the cooling performance of a microchannel heat sink
Authors:Jung Yim Min
Affiliation:Department of Mechanical Engineering, Korea Advanced Institute of Science and Technology, Taejon 305-701, South Korea
Abstract:In this paper, the effect of tip clearance on the cooling performance of the microchannel heat sink is presented under the fixed pumping power condition. The thermal resistance of a microchannel heat sink is defined for evaluating its cooling performance. The effect of tip clearance is numerically investigated by increasing tip clearance from zero under the fixed pumping power condition. From the numerical results, the optimized tip clearance is determined, for which the thermal resistance has a minimum value. Finally, we show that the presence of tip clearance can improve the cooling performance of a microchannel heat sink when tip clearance is smaller than a channel width.
Keywords:Microchannel heat sink   Tip clearance   Thermal resistance   Pumping power condition