首页 | 本学科首页   官方微博 | 高级检索  
     

Two-stage numerical simulation for temperature profile in furnace of tangentially fired pulverized coal boiler
作者姓名:周乃君  徐琼辉  周萍
作者单位:SchoolofEnergyandPowerEngineering,CentralSouthUniversity,Changsha410083,China
摘    要:Considering the fact that the temperature distribution in furnace of a tangential fired pulverized coal boiler is difficult to be measured and monitored, two-stage numerical simulation method was put forward. First, multifield coupling simulation in typical work conditions was carried out off-line with the software CFX-4.3, and then the expression of temperature profile varying with operating parameter was obtained. According to real-time operating parameters, the temperature at arbitrary point of the furnace can be calculated by using this expression. Thus the temperature profile can be shown on-line and monitoring for combustion state in the furnace is realized. The simulation model was checked by the parameters measured in an operating boiler, DO130-9. 8/540. The maximum of relative error is less than 12% and the absolute error is less than 120℃, which shows that the proposed two-stage simulation method is reliable and able to satisfy the requirement of industrial application.

关 键 词:粉煤锅炉  燃烧监测  温度分布  数值模拟
收稿时间:10 March 2004
修稿时间:11 June 2004

Two-stage numerical simulation for temperature profile in furnace of tangentially fired pulverized coal boiler
Zhou Nai-jun , Xu Qiong-hui and Zhou Ping.Two-stage numerical simulation for temperature profile in furnace of tangentially fired pulverized coal boiler[J].Journal of Central South University of Technology,2005,12(1):97-101.
Authors:Zhou Nai-jun  Xu Qiong-hui and Zhou Ping
Affiliation:(1) School of Energy and Power Engineering, Central South University, 410083 Changsha, China
Abstract:Considering the fact that the temperature distribution in furnace of a tangential fired pulverized coal boiler is difficult to be measured and monitored, two-stage numerical simulation method was put forward. First, multi-field coupling simulation in typical work conditions was carried out off-line with the software CFX-4.3, and then the expression of temperature profile varying with operating parameter was obtained. According to real-time operating parameters, the temperature at arbitrary point of the furnace can be calculated by using this expression. Thus the temperature profile can be shown on-line and monitoring for combustion state in the furnace is realized. The simul-ation model was checked by the parameters measured in an operating boiler, DG130-9.8/540. The maximum of relative error is less than 12% and the absolute error is less than 120 ℃, which shows that the proposed two-stage simulation method is reliable and able to satisfy the requirement of industrial application.
Keywords:pulverized coal boiler  combustion monitoring  temperature distribution  numerical simulation