首页 | 本学科首页   官方微博 | 高级检索  
     


Parameter estimation of a transformer with saturation using inrush measurements
Authors:S. Bogarra  A. Font  I. Candela  J. Pedra
Affiliation:1. Department of Electrical Engineering, ETSEIT-UPC, Colom 1, 08222 Terrassa, Spain;2. Department of Electrical Engineering, ETSEIB-UPC, Av. Diagonal 647, 08028 Barcelona, Spain
Abstract:This paper presents a method to compute the parameters of a transformer model with saturation using the voltage and current waveforms of an inrush test and a no-load test. The transformer is modeled with their electric and magnetic equivalent circuits and a single-valued function that characterizes its non-linear magnetic behavior. A 3-kVA single-phase transformer and a 5-kVA three-phase three-legged transformer have been tested in the laboratory. The method to obtain the parameters of the non-linear flux–current relation that characterize the saturation has been described in the paper. The analytical function used to adjust the experimental measurements fits them very well.
Keywords:Transformer modeling   Parameter estimation   Inrush current
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏