110kV GIS设备SF_6气室压力异常升高的处理
引用本文:张建华,陶瑞基,袁文雄. 110kV GIS设备SF_6气室压力异常升高的处理[J]. 高压电器, 2012, 48(2): 107-109
作者姓名:张建华  陶瑞基  袁文雄
作者单位:广东省韶关钢铁集团有限公司,广东,512123
摘    要:针对韶钢某变电站110 kV的GIS设备一SF6气室压力异常升高的情况,判断是气室内漏造成的结果,并采取了检查、更换气室盆式绝缘子的处理措施,恢复了气室的正常压力,确保了该站GIS设备的正常运行。提出了3点建议,避免类似故障的发生。

关 键 词:GIS设备  内漏  SF6气体  检修

Dealing with Abnormal Pressure Rising in SF6 Gas Chamber of 110 kV GIS Equipment
ZHANG Jian-hua , TAO Rui-ji , YUAN Wen-xiong. Dealing with Abnormal Pressure Rising in SF6 Gas Chamber of 110 kV GIS Equipment[J]. High Voltage Apparatus, 2012, 48(2): 107-109
Authors:ZHANG Jian-hua    TAO Rui-ji    YUAN Wen-xiong
Affiliation:(Shaoguan Iron & Steel Group Co.,Ltd.,Guangdong 512123,China)
Abstract:A fault of abnormal pressure raising in the SF6 gas chamber of 110 kV GIS in a substation at Shaoguan Iron & Steel Group Co.,Ltd.was analyzed,and the cause was judged to be the air-leakage.Then the chamber was checked,and the pot-type insulator was replaced.Consequently,the pressure of the gas chamber was recovered.Puts forward three suggestions are offered in this paper to avoid this kind of fault.
Keywords:GIS equipment  leakage  SF6 gas  maintenance