首页 | 本学科首页   官方微博 | 高级检索  
     


A New Distribution System Reconfiguration Approach Using Optimum Power Flow and Sensitivity Analysis for Loss Reduction
Authors:Gomes  FV Carneiro  S  Jr Pereira  JLR Vinagre  MP Garcia  PAN De Araujo  LR
Affiliation:Dept. of Electr. Eng., Fed. Univ. Fed. de Juiz de Fora;
Abstract:This paper presents a new approach for distribution system reconfiguration (DSR) based on optimum power flow (OPF) in which the branch statuses (open/close) are represented by continuous functions. In the proposed approach, all branches are initially considered closed, and from the OPF results, a heuristic technique is used to determine the next loop to be broken by opening one switch. Then the list of switches that are candidates to be opened is updated, and the above process is repeated until all loops are broken, making the distribution system radial. This paper includes results and comparisons on test systems utilized in three classical papers published in the technical literature, as well as in a previous paper by the authors. Results obtained on a real large-scale distribution system are also presented
Keywords: