首页 | 本学科首页   官方微博 | 高级检索  
     

220kV GIS漏气缺陷原因分析及处理措施
引用本文:周永强,刘晓冬,周开峰. 220kV GIS漏气缺陷原因分析及处理措施[J]. 河北电力技术, 2011, 30(4): 34+43-34,43
作者姓名:周永强  刘晓冬  周开峰
作者单位:1. 保定供电公司,河北 保定,071051
2. 河北省电力研究院,石家庄,050021
摘    要:针对某变电站一起220 kV GIS漏气缺陷,进行原因分析,认为GIS法兰密封面漏涂防水密封胶是220 kV GIS漏气的原因,并提出处理措施及建议.

关 键 词:220 kV变电站  GIS  漏气  螺栓

Cause Analysis and Settlement Measures on 220 kV Gas Insulation Substation Gas Leakage
Zhou Yongqiang,Liu Xiaodong,Zhou Kaifeng. Cause Analysis and Settlement Measures on 220 kV Gas Insulation Substation Gas Leakage[J]. Hebei Electric Power, 2011, 30(4): 34+43-34,43
Authors:Zhou Yongqiang  Liu Xiaodong  Zhou Kaifeng
Affiliation:Zhou Yongqiang,Liu Xiaodong,Zhou Kaifeng
Abstract:This paper introduces that some substation 220 kV GIS with air leakage cause analysis of defects,considers the causes of leakage of the main reasons is the GIS flange seal surface due to missing coating waterproofing sealant,and proposes the targeted treatment.
Keywords:220 kV substation  gas insulation substation  gas leakage  bolt  
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号