首页 | 本学科首页   官方微博 | 高级检索  
     

华东电网2.20污闪事故的分析和思考
引用本文:张宇,肖嵘. 华东电网2.20污闪事故的分析和思考[J]. 华东电力, 2004, 32(9): 17-22
作者姓名:张宇  肖嵘
作者单位:华东电力试验研究院,上海,200437;华东电力试验研究院,上海,200437
摘    要:2004年2月19日至20日,一场罕见的持续大雾,造成上海、浙江和江苏的6回500kV线路多次污闪跳闸。介绍了事故情况并详细分析了这几起局部污闪的原因,针对这系列污闪事故提出了相应的反事故措施,探讨了500kV线路防污工作的方向。

关 键 词:污闪  绝缘子  选型  反措
文章编号:1001-9529(2004)09-0017-06
修稿时间:2004-03-24

Analysis and considerations of 2.20 pollution flashover accident in East China Power Grid
ZHANG Yu,XIAO Rong. Analysis and considerations of 2.20 pollution flashover accident in East China Power Grid[J]. East China Electric Power, 2004, 32(9): 17-22
Authors:ZHANG Yu  XIAO Rong
Abstract:Pollution flashover caused multiple trips of six 500 kV lines in Shanghai, Zhejiang and Jiangsu provinces due to an unusual heavy fog from Jan. 19 to 20 of 2004. The process of the accident was introduced and reasons of the partial pollution flashover were analyzed. Aiming at this series of pollution flashover accidents relevant anti-failure countermeasures were put forward and the destination of anti-pollution work for 500 kV lines was discussed.
Keywords:pollution flashover  insulator  type selection  countermeasures
本文献已被 CNKI 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号