首页 | 本学科首页   官方微博 | 高级检索  
     

冶金自备电厂发电机差动保护误动分析
引用本文:高彩玲.冶金自备电厂发电机差动保护误动分析[J].冶金动力,2009(1):1-3.
作者姓名:高彩玲
作者单位:酒泉钢铁集团公司设计研究院,甘肃嘉峪关,735100
摘    要:发电机的差动保护误动对电力系统影响非常大,在采用了微机保护装置以后,能智能地记录下故障时的系统情况,给故障分析提供第一手的资料。根据所掌握的录波波形进行分析,发现误动原因是一次暂态特性的差异。还对设计运行单位提出了建议,以避免此类事故的发生。

关 键 词:发电机差动保护  电流互感器暂态特性  故障录波

Analysis of Differential Protection Misoperation of Generator for Metallurgic Industrial Power Plant
GAO Cai-ling.Analysis of Differential Protection Misoperation of Generator for Metallurgic Industrial Power Plant[J].Metallurgical Power,2009(1):1-3.
Authors:GAO Cai-ling
Affiliation:GAO Cai-ling (Design and Research Institute, Jiuquan Iron & Steel Co., Ltd., Jiayuguan, Gansu 735100)
Abstract:Differential protection misoperation of generator had a serious effect on the power system. After using microprocessor protection device, it could record faults of the system intellectually and provide first-hand data for analysis of the faults. Based on analysis of the wave shape recorded, it found out that misoperation causes were differences of transient char- acteristics.Some suggestions were offer to the design unit to avoid such accidents.
Keywords:differential protection misoperation of generator  transient characteristic ofcurrent transformer  fault wave shape recorded