基于混合无源控制的变换器并联研究
引用本文:刘卫朋,崔晓锋,侯明宣,吴尚.基于混合无源控制的变换器并联研究[J].电测与仪表,2023,60(8):26-31.
作者姓名:刘卫朋  崔晓锋  侯明宣  吴尚
作者单位:河北工业大学,河北工业大学,河北工业大学,河北工业大学
基金项目:国家自然科学基金资助项目(61941303);国家自然科学基金资助项目(62073118);国家自然科学基金资助项目(62073117);中央引导地方科技发展资金项目(206Z1701G);河北省自然科学基金资助项目(F2020202009);河北省重点研发计划项目(20271804D)
摘    要:由于线路阻抗的不同和负载的变化,直流微电网中各功率单元会出现电流分配不均和直流母线电压的波动。针对以上问题,在传统无源控制的基础上增加外部电压闭环和线路阻抗补偿电路,提出了一种将无源控制与PI控制相结合的混合无源控制策略。该方法不仅能快速跟踪负载变化且没有静态误差,而且可以有效地提高由于线路阻抗的不同而引起的并联变换器的输出电流分配精度。通过仿真表明,混合无源控制策略相比于传统的无源控制,在负载发生变化时,直流母线电压可以保持稳定,同时也提高了分流精度。通过搭建硬件在环测试的RT-LAB实时仿真平台,进一步验证了混合无源控制策略的可行性。

关 键 词:直流微电网  混合无源控制  稳定性  分流精度  实时仿真
收稿时间:2020/11/11 0:00:00
修稿时间:2020/12/24 0:00:00

Research on the parallel connection of converters based on hybrid Passivity-Based Control
Liu Weipeng,Cui Xiaofeng,Hou Mingxuan and Wu Shang.Research on the parallel connection of converters based on hybrid Passivity-Based Control[J].Electrical Measurement & Instrumentation,2023,60(8):26-31.
Authors:Liu Weipeng  Cui Xiaofeng  Hou Mingxuan and Wu Shang
Affiliation:Hebei University of Technology,Hebei University of Technology,Hebei University of Technology,Hebei University of Technology
Abstract:Due to the difference of the line impedance and the change of the load in the DC microgrid, the circulating current and the fluctuation of the DC bus voltage will be generated between the power units. In order to solve the above problems, this paper proposes a hybrid Passivity-Based Control strategy that combines Passivity-Based Control and PI control. On the basis of traditional Passivity-Based Control, an external voltage closed loop and line impedance compensation circuit are added. This method can not only track the interference quickly without static error, but also effectively suppress the circulating current between parallel converters caused by the difference in line impedance. The simulation shows that the hybrid Passivity-Based Control strategy has lower circulating current when the load changes than the traditional passive control, and keeps the DC bus voltage stable. Finally, the effectiveness of the control strategy is further verified by using the RT-LAB real-time simulation platform for hardware-in-the-loop testing.
Keywords:DC microgrid  hybrid Passivity-Based Control  circulating current  stability  real-time simulation  