首页 | 本学科首页   官方微博 | 高级检索  
     

配网结构对电压质量的影响及无功补偿对策
引用本文:诸葛斌.配网结构对电压质量的影响及无功补偿对策[J].电力电容器与无功补偿,2007,28(5).
作者姓名:诸葛斌
作者单位:桐庐县供电局,浙江,桐庐,311500
摘    要:通过对桐庐县供电局10kV配网结构的分析,对线路供电半径长,负荷变化较大,无功消耗多等问题,提出了因地制宜的解决方法和对策,合理选择配变的额定电压和档位设置,开展10kV线路无功自动补偿,解决了电压合格率低的问题。针对波动性负荷相互影响导致电机烧损等事故的处理,通过优化静态无功配置,在不投入动态无功补偿设备的条件下,低成本的技术措施缓解了10kV线路电压骤升、骤降对电机运行的影响,使得各用户能投入正常运行。

关 键 词:配网结构  电压质量  无功配置  对策

Influence of Distributing Network Structure on Voltage Quality and Reactive Compensation Coumtermeasures
ZHU Ge-bin.Influence of Distributing Network Structure on Voltage Quality and Reactive Compensation Coumtermeasures[J].Power Capacitor $ Reactive Power Compensation,2007,28(5).
Authors:ZHU Ge-bin
Abstract:With analyzing the 10kV distributing network structure in Tonglu,the method and strategy of selecting transformer taps reasonably and compensating reactive power automatically in 10kV line were provided in this paper,which improved the voltage quality preferably.Configuring static compensation equipment optimally was a effective method to resolve the problem of fluctuated load disturbed each other resulting in electric machine burning out.Low cost way was used to mitigate the effect of voltage dip or swell and make each motor running stably.
Keywords:Distributing network structure  Voltage quality  Reactive configure  Coumtermeasures