Abstract: | This paper deals with a new detection method based on three‐phase vector operation for voltage sag. The detection method is applicable to a protection system using a high‐speed interruption system which protects distributed generators and critical loads in a customer's facility. The algorithm and merits of this method are explained in detail. The detection characteristics are then analyzed using the ATP (Alternative Transients Program) and are confirmed using a real‐time digital simulator, and it is shown that the method is useful for detecting voltage sag. © 2005 Wiley Periodicals, Inc. Electr Eng Jpn, 152(4): 34–41, 2005; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/eej.20117 |