10 kV电磁式电压互感器爆炸的原因和解决方案
引用本文:林泉. 10 kV电磁式电压互感器爆炸的原因和解决方案[J]. 电力设备, 2005, 6(12): 71-73
作者姓名:林泉
作者单位:北京电力公司大兴供电公司,北京市,102600
摘    要:分析了2起10kV电磁式电压互感器(TV)爆炸的原因,提出了在2个变电站分别采用更换开关特性优良的开关和加入一个特殊设计的第4TV的解决方案,满足了各自的运行要求。文章还阐述了中压电网中常见的过电压类型——操作过电压和铁磁谐振过电压的形成原因和发展机理,提出了几种行之有效的解决方案。

关 键 词:过电压  电压互感器  事故分析  铁磁谐振  操作过电压  供用电
收稿时间:2005-10-26
修稿时间:2005-10-26

Explosive Reason and Solving Scheme of 10 kV Electromagnetic Type Voltage Transformer
LIN Quan. Explosive Reason and Solving Scheme of 10 kV Electromagnetic Type Voltage Transformer[J]. Electrical Equipment, 2005, 6(12): 71-73
Authors:LIN Quan
Affiliation:Daxing Power Supply Co., Beijing Electric Power Company, Beijing 102600,China
Abstract:The explosive reasons for two 10 kV electromagnetic type voltage transformers (TV) were analyzed. The schemes for 2 substations to adopt the switch scheme and 4 TV scheme respectively were put forward. The paper elaborated the common over voltage type in medium voltage power network-the forming reason and developing mechanism for operating over voltage and ferro-resonance over voltage, and some kinds of effective solving scheme were presented.
Keywords:over voltage   voltage transformer   fault analysis   ferro - resonance   operating over voltage   power supply and consumption