首页 | 本学科首页   官方微博 | 高级检索  
     

相控断路器在抑制35kV并联电抗器操作过电压中的应用
引用本文:郑一鸣,杨松伟,何文林,徐华,闫东,邵先军,赵琳,骆阗彦.相控断路器在抑制35kV并联电抗器操作过电压中的应用[J].电力自动化设备,2019,39(2).
作者姓名:郑一鸣  杨松伟  何文林  徐华  闫东  邵先军  赵琳  骆阗彦
作者单位:国网浙江省电力有限公司电力科学研究院,浙江杭州,310014;国网浙江省电力有限公司,浙江杭州,310007;国网浙江省电力有限公司丽水供电公司,浙江丽水,323050
摘    要:近年来我国频繁发生220 kV变电站35 kV并联电抗器切除时操作过电压导致的设备故障,危及电网安全稳定运行。对切除并联电抗器过电压产生的机理、危害和抑制进行系统分析,提出了并联电抗器的选相投切策略,并开展了现场过电压实测和PSCAD仿真分析,为35 kV并联电抗器操作过电压的抑制提供了解决思路和工程经验。

关 键 词:并联电抗器  相控断路器  操作过电压  暂态仿真

Application of phase controlled circuit breakers in overvoltage suppression for 35 kV shunt reactor
ZHENG Yiming,YANG Songwei,HE Wenlin,XU Hu,YAN Dong,SHAO Xianjun,ZHAO Lin and LUO Tianyan.Application of phase controlled circuit breakers in overvoltage suppression for 35 kV shunt reactor[J].Electric Power Automation Equipment,2019,39(2).
Authors:ZHENG Yiming  YANG Songwei  HE Wenlin  XU Hu  YAN Dong  SHAO Xianjun  ZHAO Lin and LUO Tianyan
Affiliation:Electric Power Research Institute of State Grid Zhejiang Electric Power Co.,Ltd.,Hangzhou 310014, China,State Grid Zhejiang Electric Power Co.,Ltd.,Hangzhou 310007, China,Electric Power Research Institute of State Grid Zhejiang Electric Power Co.,Ltd.,Hangzhou 310014, China,State Grid Zhejiang Electric Power Co.,Ltd.,Hangzhou 310007, China,Lishui Power Supply Company of State Grid Zhejiang Electric Power Co.,Ltd.,Lishui 323050, China,Electric Power Research Institute of State Grid Zhejiang Electric Power Co.,Ltd.,Hangzhou 310014, China,Electric Power Research Institute of State Grid Zhejiang Electric Power Co.,Ltd.,Hangzhou 310014, China and Electric Power Research Institute of State Grid Zhejiang Electric Power Co.,Ltd.,Hangzhou 310014, China
Abstract:In recent years, equipment breakdowns caused by overvoltage during 35 kV shunt reactor switching in 220 kV substations frequently occur in China, which endangers the safe and stable operation of power grid. The mechanism, perniciousness and suppression of shunt reactor switching overvoltage are systematically analyzed. The strategy of phase controlled circuit breaker is proposed, and the field overvoltage measurement and PSCAD simulation analysis are carried out, which provides solutions and engineering experiences for the switching overvoltage suppression of 35 kV shunt reactor.
Keywords:shunt reactor  phase controlled circuit breaker  operation overvoltage  transient simulation
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电力自动化设备》浏览原始摘要信息
点击此处可从《电力自动化设备》下载全文