首页 | 本学科首页   官方微博 | 高级检索  
     


Practical Control Implementation of a Three- to Single-Phase Online UPS
Authors:Eung-Ho Kim Jung-Min Kwon Jae-Kyu Park Bong-Hwan Kwon
Affiliation:Dept. of Electron. & Electr. Eng., Pohang Univ. of Sci. & Technol., Pohang;
Abstract: A high-performance three- to single-phase online uninterruptible power supply (UPS) is proposed. The proposed UPS is composed of a rectifier, a battery charger/discharger, and an inverter. The rectifier has the capability of power-factor correction and regulates a dc-link voltage. When the rectifier becomes unavailable or when the current required by the load exceeds the output rating of the rectifier, the charger/discharger supplies the power demanded by the load to a dc-link capacitor. The inverter provides a regulated sinusoidal output voltage and limits an output current under an impulsive load. New control algorithms of the rectifier, the charger/discharger, and the inverter are proposed. The proposed algorithms of the rectifier and the charger/discharger improve dynamic performance at step load change. To improve the transient response of the output voltage at outage of an input source, a mode change method of the charger/discharger is also proposed. Additionally, the proposed current-limit algorithm of the inverter can be implemented without additional hardware, and it increases the reliability of the UPS.