首页 | 本学科首页   官方微博 | 高级检索  
     

光照发电厂轴瓦温度跳变的原因分析及处理
引用本文:李春明.光照发电厂轴瓦温度跳变的原因分析及处理[J].贵州电力技术,2011(3):84-86.
作者姓名:李春明
作者单位:贵州黔源北盘江光照发电厂,贵州晴隆561405
摘    要:机组轴承的测温电阻质量参差不齐,不能满足运行要求。测温电阻电缆长期浸泡在导轴承、推力轴承油槽里,使电缆外皮变硬变脆,很难弯折。电缆表面出现很多裂纹,长期受高温油流的冲击,造成运行中测温电阻电缆断裂。机组长时间运行在振动区.造成测温回路端子松动。电缆与测温电阻端部出现虚焊。

关 键 词:发电厂  测温电阻  分析原因  应对措施

Reasons analysis and treatment on the hopping of unit bearing temperature in the Guan gzhao Hydropower Plant
Li Chunming.Reasons analysis and treatment on the hopping of unit bearing temperature in the Guan gzhao Hydropower Plant[J].Guizhou Electric Power Technology,2011(3):84-86.
Authors:Li Chunming
Affiliation:Li Chunming ( Guangzhao Power Plant, Qinglong 561405 Guizhou, China)
Abstract:Temperature sensors is an important resistance in the Hydropower plant. Temperature measurement system of bearing unit plays an important role in the monitoring system of Hydropower plant. The operating conditions will affect the safe operation of generators. Four units of the Guang Zhao Hydropower Plant has been put into operation since 2008, unit bearing temperature appears false positives and hopping. This phenomenon has been plagued by operation personnel of power plant.
Keywords:power plant  temperature resistance  reasons analysis  treatment