高压SF_6断路器的喷管外击穿现象
引用本文:刘卫东 Jone.,GR. 高压SF_6断路器的喷管外击穿现象[J]. 高压电器, 1993, 0(6): 3-9
作者姓名:刘卫东 Jone.  GR
作者单位:清华大学,利物浦大学 北京 100084,英国
摘    要:某些高压SF_6断路器在一定条件下可能出现喷管外击穿现象,即断路器断口的击穿路径发生在喷管的外表面。本文介绍了这一现象的试验研究结果。它表明这一现象的出现和喷管表面的电荷积累有关,并受电路条件和喷管的几何形状的影响。

关 键 词:六氟化硫断路器  击穿  试验  研究  高电压

Nozzle External Breakdown Phenomenon in SF_6 HV Circuit Breaker
Liu Weidong,Jones G R. Nozzle External Breakdown Phenomenon in SF_6 HV Circuit Breaker[J]. High Voltage Apparatus, 1993, 0(6): 3-9
Authors:Liu Weidong  Jones G R
Abstract:In some SF6 circuit breakers there was a probability of breakdown occurred not within the nozzle,but rather along the nozzle external surface.This paper presents some experimental results on this external breakdown phenomenon.It was demonstrated that the external breakdown may be induced by the charge accumulated on the nozzle surface and was affected by the nozzle geometry and the circuit condition.
Keywords:SF circuit breaker  breakdown  test  research  high voltage  
本文献已被 CNKI 维普 等数据库收录!