首页 | 本学科首页   官方微博 | 高级检索  
     

夏热冬冷地区被动式超低能耗绿色建筑室内热湿环境营造及实测分析
引用本文:疏志勇,吴志敏,魏燕丽,许锦峰.夏热冬冷地区被动式超低能耗绿色建筑室内热湿环境营造及实测分析[J].新型建筑材料,2019(5):146-151.
作者姓名:疏志勇  吴志敏  魏燕丽  许锦峰
作者单位:江苏省建筑科学研究院有限公司;江苏省绿色建筑与结构安全重点实验室
基金项目:“十三五”国家重点研发计划课题(2017YFC0702502);南京市建设系统科技项目(ks1510);江苏省级建筑节能专项引导资金建筑节能科技支撑项目
摘    要:对夏热冬冷地区江苏省某研发中心被动式超低能耗办公楼室内外环境参数进行为期7d的实测,并对室内外热湿环境参数进行线性拟合,考察了不同功能区的室内温湿度及舒适性。结果表明:在夏热冬冷地区室外大温湿度差的干扰下,从逐时室内温湿度来看,被动式超低能耗建筑室内温湿度受干扰很小;但在过渡季逐渐转夏季时,室内最高温度间歇性达到28℃,相对湿度基本处于70%~90%,均值为72.5%,存在着湿度大且间歇性过热的现象.良好的建筑密闭性和适当的通风是解决夏热冬冷地区室内舒适度有效的被动式节能措施。

关 键 词:被动式超低能耗建筑  夏热冬冷地区  温湿度  室内外参数  舒适度评价

Construction and measurement analysis of indoor heat and humidity environment in passive ultra-low energy green buildings in hot summer and cold winter areas
SHU Zhiyong,WU Zhimin,WEI Yanli,XU Jinfeng.Construction and measurement analysis of indoor heat and humidity environment in passive ultra-low energy green buildings in hot summer and cold winter areas[J].New Building Materials,2019(5):146-151.
Authors:SHU Zhiyong  WU Zhimin  WEI Yanli  XU Jinfeng
Affiliation:(Jiangsu Research Institute of Building Science Co.,LTD,Nanjing 210008,China;Jiangsu Province Key Laboratory of Research of Green Building and Structural Safety,Nanjing 210008,China)
Abstract:The indoor and outdoor environmental parameters of a passive ultra-low energy office building in a research and development center in Jiangsu Province in the hot summer and cold winter area were measured for one week,and the indoor and outdoor thermal and humid environment parameters were linearly fitted.The indoor temperature,humidity and comfort of different functional areas were investigated.The results show that under the disturbance of outdoor large temperature and humidity in the hot summer and cold winter regions,the indoor temperature and humidity of passive ultra-low energy buildings are less affected by the indoor temperature and humidity.However,during the transition season when it gradually turns to summer,the indoor maximum temperature intermittently reaches 28℃,the relative humidity is basically between 70%and 90%,the average value is 72.5%,there is a phenomenon of large humidity and intermittent overheating.It can be concluded that good building tightness and proper ventilation are effective passive energy saving for solving indoor comfort in hot summer and cold winter areas.
Keywords:passive ultra-low energy buildings  hot summer and cold winter areas  temperature and humidity  indoor and outdoor parameters  comfort evaluation
本文献已被 CNKI 维普 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏