空调冷冻水系统大温差设计的能耗分析
引用本文:周亚素,陈沛霖.空调冷冻水系统大温差设计的能耗分析[J].建筑热能通风空调,1999,18(2):18-19.
作者姓名:周亚素  陈沛霖
作者单位:[1]中国纺织大学 [2]同济大学
摘    要:从水泵、制冷机及空调系统的基本理论出发,分析了空调冷冻水系统大温差设计的能耗,并提出了冷冻水系统大温差设计的使用场合。由于系统虽节约了水量,减少水泵扬程及耗电量,但蒸发温度下降,冷水机组制冷效率下降,能耗增大,所以一般适用于要求水泵扬程H〉31.7m的高层建筑空调系统。

关 键 词:空调冷冻水系统  大温差  水泵扬程  制冷效率  能耗

Analysis on Energy Consumption of Large Temperature Difference in Air Conditioning Chilled Water System
Ny ZXhou Yasu and Chen Peilin.Analysis on Energy Consumption of Large Temperature Difference in Air Conditioning Chilled Water System[J].Building Energy & Environment,1999,18(2):18-19.
Authors:Ny ZXhou Yasu and Chen Peilin
Affiliation:Ny ZXhou Yasu and Chen Peilin
Abstract:Analyses the energy consumption in air conditioning chilled water systemdesigned for large temperature difference. The system, though can reduce water flow, pumpinghead and powr correspondingly, decreases evaporate temperatureand chiller efficiency.Therefore, it is commonly appied to high-rise buildings air conditioning system that demandspumping head more than 31. 7m.
Keywords:air conditioning chilled water system  large temperature difference  pumping head  chiller efficiency