首页 | 本学科首页   官方微博 | 高级检索  
     

变压器绕组介损及电容异常分析
引用本文:赵坚. 变压器绕组介损及电容异常分析[J]. 广西电力, 2010, 33(1): 14-17
作者姓名:赵坚
作者单位:广西电网公司电力科学研究院,广西,南宁,530023
摘    要:对变压器进行绕组间、绕组对铁芯间介损测量时出现负介损或介损过小、过大、电容量严重偏小等问题进行分析,发现出现异常情况的变压器,均只有铁芯引出接地,而无夹件引出接地。认为是铁芯地屏经夹件在变压器内部接地导致了异常情况的发生。建议今后在预试中碰到此类问题时,应设法采用常规方法进行复测。

关 键 词:变压器  介损  电容量  地屏  

Analysis of Abnormal Dielectric Loss and Capacitor of Transformer Winding
ZHAO Jian. Analysis of Abnormal Dielectric Loss and Capacitor of Transformer Winding[J]. Guangxi Electric Power, 2010, 33(1): 14-17
Authors:ZHAO Jian
Affiliation:Guangxi Power Grid Electric Power Research Institute;Nanning 530023;China
Abstract:Problems encountered during the measurement of transformer dielectric loss between windings or between winding and iron core,such as negative or too big,or too small value of dielectric loss or serous small value of capacitance,are analyzed. It is founded that all abnormal transformers have only iron core grounding but don't have clamp grounding. It is because iron core earth screen was grounded through clamp in transformer that leads to abnormal results. It is suggested that dielectric loss should be remea...
Keywords:transformer  dielectric loss  capacitance  earth screen  