首页 | 本学科首页   官方微博 | 高级检索  
     


Complete condensation in a vertical tube passive condenser
Affiliation:1. Department of Mechanical Engineering, Shahrood Branch, Islamic Azad University, Shahrood, Iran;2. Department of Mechanical Engineering, Quchan Branch, Islamic Azad University, Quchan, Iran;3. Fluid Mechanics, Thermal Engineering and Multiphase Flow Research Lab. (FUTURE), Department of Mechanical Engineering, Faculty of Engineering, King Mongkut''s University of Technology Thonburi (KMUTT), Bangmod, Bangkok 10140, Thailand;4. Aerospace Engineering Department, Sharif University of Technology, 14588-89694, Iran
Abstract:An experimental study is performed for the steam condensation in a vertical tube where steam is completely condensed. A condenser tube is submerged in a water pool where the heat from the condenser tube is removed through boiling heat transfer. The experiment data showed that the operating pressure is uniquely determined by inlet steam flow rate for the complete condensation. The condensation heat transfer rate increases and the condensation heat transfer coefficient decreases with the system pressure. For the condenser submerged in a saturated water pool, strong primary pressure dependency was observed on the condensation heat transfer.
Keywords:
本文献已被 ScienceDirect 等数据库收录!