A Nonisolated Single-Phase UPS Topology With 110-V/220-V Input–Output Voltage Ratings |
| |
Abstract: | A circuit configuration of a single-phase nonisolated online uninterruptible power supply (UPS) with 110-V/220-V input–output voltage ratings is proposed, allowing the bypass operation without a transformer even if the input voltage is different from the output voltage. The converter consists of an ac–dc/dc–dc three-level boost converter combined with a double half-bridge inverter. In this type of configuration size, cost and efficiency are improved due to the reduced number of switches and batteries, and also, no low-frequency isolation transformer is required to realize bypass operation because of the common neutral connection. Both stages of the proposed circuit operate at high frequency by using a passive nondissipative snubber circuit in the boost converter and insulated-gate bipolar-transistor switches in the double half-bridge inverter, with low conduction losses, low tail current, and low switching losses. Principle of operation and experimental results for a 2.6-kVA prototype are presented to demonstrate the UPS performance. |
| |
Keywords: | |
|
|