Intuitive robust stability metric for PID control of self-regulating processes
Authors:Arbogast Jeffrey E  Beauregard Brett M  Cooper Douglas J
Affiliation:University of Connecticut, Chemical Engineering Program, CMBE Department, U-3222, 191 Auditorium Rd., Storrs, CT 06269-3222, United States.
Abstract:Published methods establish how plant-model mismatch in the process gain and dead time impacts closed-loop stability. However, these methods assume no plant-model mismatch in the process time constant. The work presented here proposes the robust stability factor metric, RSF, to examine the effect of plant-model mismatch in the process gain, dead time, and time constant. The RSF is presented in two forms: an equation form and a visual form displayed on robustness plots derived from the Bode and Nyquist stability criteria. This understanding of robust stability is reinforced through visual examples of how closed-loop performance changes with various levels of plant-model mismatch. One example shows how plant-model mismatch in the time constant can impact closed-loop stability as much as plant-model mismatch in the gain and/or dead time. Theoretical discussion shows that the impact is greater for small dead time to time constant ratios. As the closed-loop time constant used in Internal Model Control (IMC) tuning decreases, the impact becomes significant for a larger range of dead time to time constant ratios. To complete the presentation, the RSF is used to compare the robust stability of IMC-PI tuning to other PI, PID, and PID with Filter tuning correlations.
Keywords:Robustness plot  Robust stability  PID  Controller tuning  IMC
本文献已被 ScienceDirect PubMed 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号