Fire spread from an open‐doors electrical cabinet to neighboring targets in a confined and mechanically ventilated facility
Authors:Pascal Zavaleta  Sylvain Suard  Laurent Audouin
Abstract:Electrical cabinet fire is one of the main fire hazards in nuclear power plants. As part of the OECD PRISME‐2 programme, four fire tests were carried out to investigate the fire spread from an open‐doors electrical cabinet to overhead cable trays and adjacent cabinets in a confined and mechanically ventilated facility. These tests, named CFS‐5 to CFS‐7 and CORE‐6, used same both cabinet (fire source) and three overhead cable trays. The trays were filled with a halogenated flame‐retardant cable‐type for CFS‐5 and one halogen‐free for the three other tests. Moreover, fire dampers were used for CFS‐7 test while CORE‐6 test implemented two additional cabinets adjacent to the fire source. Measurements such as flame and gas temperature, gas concentration, mass loss rate, and heat release rate were performed for investigating the fire spread. Cabinet fire spread to the cable trays for CFS‐5 and CFS‐6 tests. Three fast and short cable tray fires were shown for CFS‐5, while a slow and long cable tray fire was highlighted for CFS‐6. In contrast, the fire dampers shutdown for CFS‐7 test prevented ignition of the overhead cables. Furthermore, for CORE‐6 test, cabinet fire spread to the adjacent cabinets, but the upper cables were not ignited.
Keywords:adjacent cabinet  DIVA facility  electrical cabinet  fire spread  overhead cable trays