750kV同塔双回输电线路雷击塔顶感应电压的数值计算
引用本文:高媛,郭洁,雷娟,郭志涛.750kV同塔双回输电线路雷击塔顶感应电压的数值计算[J].电瓷避雷器,2007(3):29-32.
作者姓名:高媛  郭洁  雷娟  郭志涛
作者单位:西安交通大学,西安,710049
基金项目:国家自然科学基金(No.50577051)
摘    要:架空输电线路的雷击感应电压计算是电力线路绝缘设计、采取防雷保护措施的基础计算。对雷击750kV同塔双回输电线路塔顶产生感应电压的暂态过程进行了分析,采用电磁场数值分析方法,建立了回击电流模型和线路耦合模型,精确地计算了感应电压值。计算结果表明,感应电压随时间变化非常快,所以在计算雷击塔顶的耐雷水平时,如果把感应电压以一个恒定值的方式计入,必然会产生一定的误差,应该考虑感应电压的暂态过程。

关 键 词:750kV输电线路  感应电压计算  回击模型  耦合模型
文章编号:1003-8337(2007)03-0029-04
修稿时间:2007-04-23

Calculation of Lightning Induced Voltage on 750kV Double Circuit Transmission Lines on the Same Tower when Lightning Strikes Tower Top
GAO Yuan,GUO Jie,LEI Juan,GUO Zhi-tao.Calculation of Lightning Induced Voltage on 750kV Double Circuit Transmission Lines on the Same Tower when Lightning Strikes Tower Top[J].Insulators and Surge Arresters,2007(3):29-32.
Authors:GAO Yuan  GUO Jie  LEI Juan  GUO Zhi-tao
Abstract:Lightning induced voltage on overhead transmission lines is related to the basic calculation of insulation design and lightning protection measure.The author presents analytical expressions for transient process of lightning-induced voltages when lightning strikes the tower top of 750 kV double circuit transmission lines on the same tower.The procedure makes use of a lightning return-stroke model for the calculation of the lightning electromagnetic field and a coupling model already presented in the literature based on the transmission line theory for field-to-overhead line coupling calculations.The result of calculations shows that variation of lightning induced voltage with time is very fast.There is a consequential error if we still regard lightning induced voltage as invariable to calculating of lightning withstand level.So the transient process of lightning induced voltage should be taken into account.
Keywords:750 kV transmission line  calculation of lightning induced voltage  return-stroke model  coupling model