首页 | 本学科首页   官方微博 | 高级检索  
     


Experimental investigation of heat transfer in an air duct with an inclined heating surface
Authors:M S Hatamipour  D Mowla
Affiliation:Department of Chemical Engineering, School of Engineering , Shiraz University , Shiraz , Iran
Abstract:In this paper some experimental results showing the influence of inclination of a cylindrical heating surface immersed in an air duct on heat transfer coefficient are presented. The experiments were performed in a laboratory-scaled apparatus of square cross section with dimensions 120 ‐ 120 mm and 1400 mm in height. Heat transfer surface was an electrical heater made of brass tube with outer diameter of 19 mm and 110 mm length. In each experiment the temperatures of the front and rear side of the heating surface, inclination angle, air velocity, inlet air temperature, and heater power were measured. It was concluded that heat transfer coefficient depends on flow conditions and angle of inclination. The maximum Nusselt number (Nu) was observed to occur about 45° inclination relative to the horizon, for the range of Reynolds numbers used in experiments. The values of heat transfercoefficients in the vertical position were very nearly the same as they were in the horizontal position. Based on the experimental results, a correlation was proposed for estimation of Nu at the desired flow velocity and inclination angle, relative to Nu at zero inclination.
Keywords:Forced Convection  Heat Transfer Coefficient  Inclination Angle
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号