首页 | 本学科首页   官方微博 | 高级检索  
     


Factors of hetero space charge generation in XLPE under dc electric field of 20 kV/mm
Authors:Toshinao Takeda  Naohiro Hozumi  Hiroshi Suzuki  Tatsuki Okamoto
Abstract:This report deals with the mechanism of space charge accumulation in cross‐linked polyethylene (XLPE) under dc electric field. Space charge was measured by the pulsed‐electroacoustic method with applying dc stress of 20 kV/mm. A large amount of hetero space charge accumulated in fresh XLPE samples. Factors influencing the space charge accumulation were analyzed in regard to cross‐linking by‐products and antioxidant. No space charge was seen when the fresh sample was degassed to remove cross‐linking by‐products. Introducing acetophenone, one of the cross‐linking by‐products, in a degassed sample produces no space charge, suggesting that acetophenone itself could not be the direct factor of space charge formation. However, heating this sample up to 150 °C results in formation of hetero space charges as in virgin samples. Hence, it is concluded that hetero space charges may be formed when impurities, such as an antioxidant, dissociate thermally with the help of acetophenone and that the dissociated products are attracted toward both electrodes under a dc field to form the hetero space charges. © 1999 Scripta Technica, Electr Eng Jpn, 129(2): 13–21, 1999
Keywords:cross‐linked polyethylene  space charge  hetero space charge  acetophenone  antioxidant
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号