500 kV变电站直流电源系统级差配合特性分析及建议
引用本文:董汉彬,张明丽,蒋 枝,李淑琦,罗 洋,李晶,王嘉易. 500 kV变电站直流电源系统级差配合特性分析及建议[J]. 四川电力技术, 2023, 46(2): 84-88
作者姓名:董汉彬  张明丽  蒋 枝  李淑琦  罗 洋  李晶  王嘉易
作者单位:国网四川省电力公司电力科学研究院;东方电气(成都)工程设计咨询有限公司;国网四川省电力公司特高压直流中心
基金项目:国家重点研发计划项目(2022YFF01060);国网四川省电力公司科技项目(52199723001B)
摘    要:文中以某500 kV变电站直流电源系统交接试验中保护电器的越级跳闸为例对级差配合进行分析。首先,通过梳理直流电源系统各参数间的约束关系,对该工程级差配合存在的问题进行了研究;然后,根据该工程具体设备配置和整改难度,提出以减少直流分电柜进线段电缆截面的方法来控制短路电流水平进而实现上下级保护的级差配合。所提整改方案实施后通过了级差配合试验。

关 键 词:直流电源  级差配合  直流保护电器

Characteristic Analysis and Suggestion for Stage Difference Coordination of DC Power Supply System of 500 kV Substation
DONG Hanbin,ZHANG Mingli,JIANG Zhi,LI Shuqi,LUO Yang,LI Jing,WANG Jiayi. Characteristic Analysis and Suggestion for Stage Difference Coordination of DC Power Supply System of 500 kV Substation[J]. Sichuan Electric Power Technology, 2023, 46(2): 84-88
Authors:DONG Hanbin  ZHANG Mingli  JIANG Zhi  LI Shuqi  LUO Yang  LI Jing  WANG Jiayi
Affiliation:State Grid Sichuan Electric Power Research Institute;Dongfang Electric Engineering & Consulting Co., Ltd.;State Grid Sichuan Electric Power UHVDC Center
Abstract:Taking override trip of protective device in DC power supply system of a 500 kV substation during hand-over test for example,the stage difference coordination is analyzed. Firstly, according to the constraints on parameters of DC power supply system, the problems existing in stage difference coordination is studied. And then, based on the detailed configuration and rectification difficulty, a solution is proposed to realized the stage difference coordination between upper-stage protection and lower-stage protection by reducing the DC cable section to control short-sircuit current level. Finally, the effectiveness of the proposed method is verified by experiments.
Keywords:DC power supply  stage difference coordination   DC protective devices