Theoretical analysis of low-temperature hot source driven two-stage LiBr/H2O absorption refrigeration system |
| |
Authors: | WB Ma SM Deng |
| |
Affiliation: | Guangzhou Institute of Energy Conversion, Chinese Academy of Sciences, 81 Central Martyrs' Road, Guangzhou, China;Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong |
| |
Abstract: | A detailed theoretical analysis is presented for a two-stage LiBr/H2O absorption refrigeration system, which consists of an evaporator, a low-pressure absorber, a low-pressure generator, a high-pressure absorber, a high-pressure generator, a condenser, a low-pressure heat exchanger and a high-pressure heat exchanger, driven by a low-temperature hot source. A comparison of results from the theoretical analysis and preliminary experiment indicates that the theoretical analysis developed can represent a real system with a reasonable accuracy, and is useful for future development. |
| |
Keywords: | absorption water-lithium bromide two-stageAbsorption Eau Bromure de lithium |
本文献已被 ScienceDirect 等数据库收录! |
|