首页 | 本学科首页   官方微博 | 高级检索  
     


Performance assessment of a geothermally heated building
Authors:Yildiz Kalinci  M Tolga Balta  Arif Hepbasli
Affiliation:1. Plumbing Technology, Department of Technical Programs, Izmir Vocational School, Dokuz Eylül University, Education Campus Buca, Izmir, Turkey;2. Department of Mechanical Engineering, Faculty of Engineering, Ege University, 35100 Bornova, Izmir, Turkey
Abstract:This study deals with an exergetic performance evaluation of a geothermally heated building. This building used in the analysis has a volume of 1147.03 m3 and a net floor area of 95.59 m2, while indoor and exterior air temperatures are 20 and 0 °C, respectively. The geothermal heating system used for the heat production was constructed in the Ozkilcik heating center, Izmir, Turkey. Thermal water has a pressure of 6.8 bar, a temperature of 122 °C and a mass flow rate of 54.73 kg/s, while it is reinjected at 3.2 bar and 72 °C. The system investigated feeds three regions. Among these, the Ozkanlar region has supply/return pressure and temperature values of 4.6/3 bar and 80/60 °C, respectively. Energy and exergy flows are studied to quantify and illustrate exergy destructions in the overall system. Total exergy input rate to the system is found to be 9.92 kW and the largest exergy destruction rate occurs in the primary energy transformation at 3.85 kW.
Keywords:Exergy analysis  Low exergy  Geothermal energy
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏