首页 | 本学科首页   官方微博 | 高级检索  
     

750kV GIS变电站VFTO特性分析
引用本文:卢鹏.750kV GIS变电站VFTO特性分析[J].电力建设,2011,32(1):86-90.
作者姓名:卢鹏
作者单位:河南平高电气股份有限公司
摘    要:为评估特快速暂态过电压(very fast transient overvoltage,VFTO)特性及其对主要电气设备的危害,结合我国西北电网中某750 kV气体绝缘金属封闭开关设备(gas-insulated metal-enclosed switchgear,GIS)变电站,进行了大量的仿真计算,初步掌握了GIS...

关 键 词:750  kV  GIS  变电站  快速暂态过电压(VFTO)  过电压  隔离开关
收稿时间:2010-02-23
修稿时间:2010-10-21

Study on VFTO of 750kV GIS Substation
LU Peng.Study on VFTO of 750kV GIS Substation[J].Electric Power Construction,2011,32(1):86-90.
Authors:LU Peng
Affiliation:LU Peng(He’nan Pinggao Electric Co.Ltd.,Pingdingshan 467001,He’nan Province,China)
Abstract:In order to evaluate characteristics of VFTO and its harm to the main electrical equipment, we have done a great quantity of emulational calculations integrating with a certain 750kV GIS Substation in Northwest Power Grid of China. In the process, preliminarily, we have mastered the distribution of VFTO on main parts inside and outside of GIS and made a conclusion that the VFTO amplitude limit is in withstand capability of the relative equipment of this substation. We performed measurement on site based on the calculations, mastered important characteristic parameters, such as actual amplitude, wave shape, frequency and so on of VFTO in 750kV GIS substation. The measured results on site have instructive significance for the switching operation of disconnector of 750kV GIS, meanwhile, it made us accumulate valuable experience and data for actual measurement of VFTO and switching operation of UHV 1 100kV GIS.
Keywords:750 kV gas-insulated metal-enclosed switchgear(GIS)  substation  very fast transient overvoltage(VFTO)  overvoltage  disconnector
本文献已被 CNKI 维普 等数据库收录!
点击此处可从《电力建设》浏览原始摘要信息
点击此处可从《电力建设》下载全文