首页 | 本学科首页   官方微博 | 高级检索  
     

35kV母线CVT高压侧熔断器异常爆裂原因及解决方案研究
引用本文:唐朝,彭勤裕,焦肃山,宋小卫,汤建中,丁然,卢继平. 35kV母线CVT高压侧熔断器异常爆裂原因及解决方案研究[J]. 电力系统保护与控制, 2008, 36(20): 86-90
作者姓名:唐朝  彭勤裕  焦肃山  宋小卫  汤建中  丁然  卢继平
作者单位:重庆大学输配电装备及系统安全与新技术国家重点实验室,天水超高压输变电公司,平凉供电公司,西北电网有限公司兰州建设公司,天水供电公司
摘    要:为了解决甘肃天水电网35kV侧母线CVT在电力电容器合闸时,其高压侧熔断器发生异常爆裂的事故,通过对电力电容器合闸过电压的Matlab仿真分析,得到了引起该事故的原因。电力电容器合闸过程产生的过电压激发CVT中间变压器铁芯饱和,进而引发CVT内部非线性电感和电容铁磁谐振,产生谐振过电流,使熔断器发生爆裂。针对这一原因,文中从限制电力电容器合闸过电压和对CVT消谐两个方面提出了解决方案。仿真验证这些方案具有可行性。

关 键 词:CVT  过电压  铁磁谐振  阻尼器  Matlab仿真

Research on the reason of the 35 kV bus CVT high-voltage side fuse abnormal bursting and the solution scheme
TANG Chao,PENG Qin-yu,JIAO Su-shan,SONG Xiao-wei,TANG Jian-zhong,DING Ran,LU Ji-ping. Research on the reason of the 35 kV bus CVT high-voltage side fuse abnormal bursting and the solution scheme[J]. Power System Protection and Control, 2008, 36(20): 86-90
Authors:TANG Chao  PENG Qin-yu  JIAO Su-shan  SONG Xiao-wei  TANG Jian-zhong  DING Ran  LU Ji-ping
Affiliation:TANG Chao1,PENG Qin-yu2,JIAO Su-shan3,SONG Xiao-wei4,TANG Jian-zhong5,DING Ran1,LU Ji-ping1
Abstract:The fuse fixed on the high-voltage side of CVT that measures the 35kV bus voltage burst when closing the capacitors in Tianshui power network. Through using Matlab simulation to analyze the over-voltage when closing capacitors, the reason for this accident is gained .The over-voltage which is produced by closing capacitors inspires the transformer core saturation that triggers the nonlinear inductances and capacitances in CVT ferro resonance. Then over-current is produced that leads to burst in the fuse. For this reason, this paper brings forward the solutions from restricting the over-voltage in closing capacitors and eliminating resonance for CVT. Simulation verifies that these schemes are feasible.
Keywords:CVT  over-voltage  ferro resonance  damper  Matlab simulation