首页 | 本学科首页   官方微博 | 高级检索  
     

钠冷快堆反应性意外引入事故时停堆保护研究
引用本文:徐伟栋,段天英,冯伟伟,付浩. 钠冷快堆反应性意外引入事故时停堆保护研究[J]. 原子能科学技术, 2020, 54(8): 1433-1440. DOI: 10.7538/yzk.2019.youxian.0484
作者姓名:徐伟栋  段天英  冯伟伟  付浩
作者单位:中国原子能科学研究院 反应堆工程技术研究部,北京102413;生态环境部 核与辐射安全中心,北京102445
摘    要:在反应堆系统中,当反应堆处于异常工况时,如果运行参数超出保护限值,则由保护系统触发相关保护动作,以保证反应堆的状态符合事故验收准则的要求。本文将通过Simulink建立钠冷快堆主要系统模型,在发生反应性意外引入事故时,借鉴快堆事故分析中预期瞬态无停堆保护(ATWS)的分析方法,基于相应保护参数的测量误差和数据处理过程对反应堆一回路的保护参数及其整定值进行研究,并确保钠冷快堆的状态在整个反应性引入事故过程中符合钠冷快堆的事故验收准则。仿真结果表明,当发生补偿棒失控提升5 s和10 s时,目前的堆芯出口钠温、功率、功率流量比等保护参数的整定值、信号测量延迟及落棒时间可取其他值。当补偿棒失控提升15 s时,只要保证保护参数整定值、相应参数的信号测量延迟及落棒时间能使反应堆在36.45 s前进入深度次临界都是可以的。

关 键 词:钠冷快堆   反应性意外引入   保护参数整定值

Research on Shutdown Protection of Sodium-cooled Fast Reactor for Reactivity Accident Introduction
XU Weidong,DUAN Tianying,FENG Weiwei,FU Hao. Research on Shutdown Protection of Sodium-cooled Fast Reactor for Reactivity Accident Introduction[J]. Atomic Energy Science and Technology, 2020, 54(8): 1433-1440. DOI: 10.7538/yzk.2019.youxian.0484
Authors:XU Weidong  DUAN Tianying  FENG Weiwei  FU Hao
Affiliation:Division of Reactor Engineering Technology Research, China Institute of Atomic Energy, Beijing 102413, China;Nuclear and Radiation Safety Center, Ministry of Ecology and Environment, Beijing 102445, China
Abstract:In the reactor system, when the reactor is in abnormal condition, if the operation parameters exceed the protection limit, the relevant protection actions will be triggered by protection system to ensure that the state of the reactor meets the requirements of the accident acceptance criteria. The main system model of sodium-cooled fast reactor was established by Simulink in the paper. For reactivity accident introduction, the protection parameters and their setting values of the primary loop of the reactor were studied based on the measurement error and data processing of corresponding protection parameters, in the same manner as anticipated transient without scram (ATWS) for fast reactor analysis, and the state of the sodium-cooled fast reactor met the accident acceptance criteria for sodium-cooled fast reactor during the entire reactivity accident introduction. The results show that the current setting values of protection parameters, such as sodium temperature at core outlet, power and power-flow ratio as well as the signal measurement delay and the falling time of the rod can be taken from other values, when the shim rod is accidentally lifted for 5 s or 10 s. While for 15 s, as long as the setting value of the protection parameter, the signal measurement delay of the corresponding parameter and the falling time of the rod can make the reactor enter the depth subcritical before 36.45 s, the state of the reactor will still meet the requirement of the accident acceptance criteria.
Keywords:sodium-cooled fast reactor  reactivity accident introduction  setting value of protection parameter  
点击此处可从《原子能科学技术》浏览原始摘要信息
点击此处可从《原子能科学技术》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号