首页 | 本学科首页   官方微博 | 高级检索  
     

拒绝服务攻击下的弹性事件触发负荷频率控制
引用本文:刘希懋,曾阳阳.拒绝服务攻击下的弹性事件触发负荷频率控制[J].电子科技,2020,33(4):12-17.
作者姓名:刘希懋  曾阳阳
作者单位:三峡大学 电气与新能源学院,湖北 宜昌 443002
基金项目:国家自然科学基金(61603212)
摘    要:针对互联电力系统负荷频率控制通信网络带宽受限及易遭受恶意网络攻击的问题,文中研究了拒绝服务攻击下弹性事件触发机制和负荷频率控制器的联合设计问题。在拒绝服务攻击参数已知的情况下,提出了一种既能缓解通信带宽压力,又可同时消除拒绝服务攻击影响的弹性事件触发机制。文中构建了一种基于弹性事件触发机制及拒绝服务攻击的负荷频率控制时滞切换系统模型。应用分段李亚普洛夫函数对切换系统稳定性进行了分析,并进行了触发参数和控制器的联合设计。最后,通过一个两区域互联电力系统仿真验证了所提方法的有效性。

关 键 词:负荷频率控制  拒绝服务攻击  事件触发机制  网络控制系统  信息物理系统  指数稳定性  
收稿时间:2019-03-03

Resilient Event-Triggered Control of Load Frequency Control for Multi-Area Power Systems Against DoS Jamming Attacks
LIU Ximao,ZENG Yangyang.Resilient Event-Triggered Control of Load Frequency Control for Multi-Area Power Systems Against DoS Jamming Attacks[J].Electronic Science and Technology,2020,33(4):12-17.
Authors:LIU Ximao  ZENG Yangyang
Affiliation:School of Electrical Engineering & New Energy,China Three Gorges University,Yichang 443002,China
Abstract:Focusing on the scenario that the communication network of load frequency control for multi-area power systems is bandwidth-constrained and subject to Denial-of-Service attacks, the problem of the co-design for resilient event-triggered communication scheme and controller was investigated in this study. As DoS parameter is well known, a resilient event-triggered communication scheme was proposed, which could ease the pressure on network bandwidth and eliminated the impact of DoS attacks. In addition, a switched time delay system model was also formulated. The system stability was analyzed by using the piecewise Lyapunov function, and a co-design method for triggered parameter and controller was designed. Finally, the effectiveness of the proposed method was demonstrated with a two-area power system.
Keywords:load frequency control  denialof service attacks  event-triggered control  networked control system  cyber physical system  exponential stability  
点击此处可从《电子科技》浏览原始摘要信息
点击此处可从《电子科技》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号