毛细管网供暖室内环境对比实验研究
引用本文:陈金华,梁秋锦,李楠,高亚锋,刘红,杨雯芳.毛细管网供暖室内环境对比实验研究[J].土木建筑与环境工程,2018,40(2):88-94.
作者姓名:陈金华  梁秋锦  李楠  高亚锋  刘红  杨雯芳
作者单位:重庆大学三峡库区生态环境教育部重点实验室;低碳绿色建筑国际联合研究中心,重庆400045 重庆新鸥鹏地产(集团)有限公司,重庆,400010
基金项目:National International Scientific and Technology Cooperation and Exchange Projects(2014DFA62970),Chongqing Science and Technology Research and Development Base Construction Project(cstc2013gjhz90002),Chongqing Foundation and Frontier Research Program (CSTC2014jcyjA90018)国家国际科技合作与交流专项(2014DFA62970),重庆市科技研发基地建设计划(cstc2013gjhz90002),重庆市基础与前沿研究计划(CSTC2014jcyjA90018)
摘    要:对重庆地区毛细管网辐射供暖系统进行测试,分析在35℃供水工况下毛细管网顶棚、墙面、地面3种敷设方式的室内空气温度、围护结构壁面温度等参数。结果表明:在重庆地区35℃供水工况下,毛细管网顶棚、墙面、地面3种敷设方式供暖稳定时,室内人员活动区平均温度分别为16.53、16.4、16.94℃、辐射表面平均温度分别为29.21、28.17、22.98℃,纵向最大温差分别为1.76、3.16、0.3℃,水平最大温差分别为-0.26、0.59、-0.34℃,在实验条件下,该地区3种敷设方式供暖时室内温度均≥16℃,毛细管网构造层厚度与敷设位置直接影响室内舒适度。

关 键 词:毛细管网  敷设方式  辐射供暖  舒适度  capillary  floor  laying  mode  radiant  heating  thermal  comfort
收稿时间:2017/6/18 0:00:00

Comparative experimental analysis of capillary radiant heating on indoor environment
Chen Jinhu,Liang Qiujin,Li Nan,Gao Yafeng,Liu Hong and Yang Wenfang.Comparative experimental analysis of capillary radiant heating on indoor environment[J].土木建筑与环境工程,2018,40(2):88-94.
Authors:Chen Jinhu  Liang Qiujin  Li Nan  Gao Yafeng  Liu Hong and Yang Wenfang
Affiliation:Key Laboratory of Three Gorges Reservoir Region''s Eco-Environment;Ministry of Education;National Centre for International Research of Low-carbon and Green Buildings, Chongqing University, Chongqing 400045, P. R. China,Chongqing Newopen Real Estate, Co., Ltd., Chongqing 400010, P. R. China,Key Laboratory of Three Gorges Reservoir Region''s Eco-Environment;Ministry of Education;National Centre for International Research of Low-carbon and Green Buildings, Chongqing University, Chongqing 400045, P. R. China,Key Laboratory of Three Gorges Reservoir Region''s Eco-Environment;Ministry of Education;National Centre for International Research of Low-carbon and Green Buildings, Chongqing University, Chongqing 400045, P. R. China,Key Laboratory of Three Gorges Reservoir Region''s Eco-Environment;Ministry of Education;National Centre for International Research of Low-carbon and Green Buildings, Chongqing University, Chongqing 400045, P. R. China and Key Laboratory of Three Gorges Reservoir Region''s Eco-Environment;Ministry of Education;National Centre for International Research of Low-carbon and Green Buildings, Chongqing University, Chongqing 400045, P. R. China
Abstract:Tests of capillary radiant heating system in Chongqing district were carried out and indoor temperature,surface temperature of envelope in condition of three different capillary laying modes (ceiling,wall and floor) with 35 ℃ supply water temperature were analyzed.The experimental data indicates that in the three different conditions,when the temperature of the supply water is 35 ℃,the average temperature of indoor air is 16.53 ℃,16.40 ℃ and 16.94 ℃ respectively and that of radiation surface is 29.21 ℃,28.17 ℃ and 22.98 ℃ respectively.The largest vertical temperature difference tested is 1.76 ℃,3.16 ℃ and 0.3 ℃ while the largest horizontal difference tested in the direction fall is-0.26 ℃,0.59 ℃,-0.34 ℃ respectively.It is shown that the system meets the requirements of indoor temperaturel6℃ in three conditions.Both the thickness of capillary structure layer and the laying mode have an directly influence on the indoor thermal comfort.
Keywords:capillary floor  laying mode  radiant heating  thermal comfort