首页 | 本学科首页   官方微博 | 高级检索  
     

密闭空间内模块式冰蓄冷控温传热过程分析
引用本文:刘应书,贾彦翔,孙淑凤,宋魏鑫. 密闭空间内模块式冰蓄冷控温传热过程分析[J]. 化工学报, 2014, 65(6): 2085-2091. DOI: 10.3969/j.issn.0438-1157.2014.06.019
作者姓名:刘应书  贾彦翔  孙淑凤  宋魏鑫
作者单位:1. 北京科技大学机械工程学院, 北京 100083;2. 北京科技大学北京高校节能与环保工程研究中心, 北京 100083
基金项目:中央高校基本科研业务费专项资金(FRF-SD-12-007B)
摘    要:针对密闭空间内无源控温问题,通过数学建模和实验验证对模块式冰蓄冷控温传热过程及热力学特性展开研究。从冰蓄冷相变制冷理论入手,建立了蓄冷模块相变制冷数学模型,得到了蓄冷模块壁面综合传热系数、有效制冷时间以及制冷率的数学表达式,通过实验验证该模型的有效制冷时间理论值和实验值相对误差在5%以内。绘制了环境温度和相对湿度对蓄冷模块壁面综合传热系数、有效制冷时间及制冷率的影响关系曲线,表明环境温湿度与壁面综合传热系数和制冷率呈正比例变化关系;与有效制冷时间呈反比例变化关系。建立了环境温湿度相关修正系数方程,并运用该方程对蓄冷模块制冷率和有效制冷时间的数学模型进行了修正。研究结果为密闭环境中无源相变制冷的应用提供了技术依据。

关 键 词:密闭空间  冰蓄冷控温  相变  传热  热力学  
收稿时间:2013-09-10
修稿时间:2013-11-21

Analysis on heat transfer process with temperature control by module type ice storage within confined space
LIU Yingshu,JIA Yanxiang,SUN Shufeng,SONG Weixin. Analysis on heat transfer process with temperature control by module type ice storage within confined space[J]. Journal of Chemical Industry and Engineering(China), 2014, 65(6): 2085-2091. DOI: 10.3969/j.issn.0438-1157.2014.06.019
Authors:LIU Yingshu  JIA Yanxiang  SUN Shufeng  SONG Weixin
Affiliation:1. School of Mechanical Engineering, University of Science and Technology Beijing, Beijing 100083, China;2. Beijing Engineering Research Center for Energy Saving and Environmental Protection, University of Science and Technology Beijing, Beijing 100083, China
Abstract:Aiming at the passive temperature control problem in confined spaces, we investigate the heat transfer and thermodynamic characteristics of module type ice temperature control process with mathematical models and experiments. A model for phase transition refrigeration by cool storage module is established, and with the mathematical expression for wall heat transfer coefficient, effective cooling time and cooling rate are derived. The relative error between the theoretical effective cooling time and experimental one is less than 5%. The results indicate that the wall heat transfer coefficient and cooling rate are proportional to environment temperature and relative moisture, and inversely proportional to cooling time. The correction factor equation for environment temperature and moisture is established and utilized for revising the mathematical models of storage module cooling rate and effective cooling time. These results provide important reference to the application of passive phase-transition refrigeration in confined space.
Keywords:confined space  temperature control by ice storage  phase change  heat transfer  thermodynamics  
点击此处可从《化工学报》浏览原始摘要信息
点击此处可从《化工学报》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号