首页 | 本学科首页   官方微博 | 高级检索  
     

武汉泛海城市广场一期商业综合体水蓄冷动态模拟
引用本文:叶盛,张银安,石三平,张亚男,郭盛桢,毛钰荣.武汉泛海城市广场一期商业综合体水蓄冷动态模拟[J].制冷空调与电力机械,2013(6):74-79.
作者姓名:叶盛  张银安  石三平  张亚男  郭盛桢  毛钰荣
作者单位:[1]杭州华电华源环境工程有限公司,浙江杭州310000 [2]中南建筑设计院股份有限公司,湖北武汉430000 [3]杭州国电能源环境研究院有限公司,浙江杭州310000
摘    要:武汉泛海城市广场一期利用分时电价及消防水池,采用水蓄冷空调系统可达到移峰填谷、提高电网安全运行,降低用户运行费用的目的,同时满足项目LEED论证条款要求。项目的显著特点是商业综合体消防水池容积1600m3,水深8m,消防水池容积大,水位深,蓄冷量大;同时因消防水池深,在水池中间设内撑梁,通过动态模拟的方法分析了结构内撑梁对斜温层产生的影响。

关 键 词:水蓄冷  斜温层  动态模拟

Dynamic Simulation of Chilled Water Storage Air-conditioning System in Fanhai Urban Square 1~t Phase Commercial Construction in Wuhan
YE Sheng,ZHANG Yin-an,SHI San-ping,ZHANG Ya-nan,GUO Sheng-zhen,MAO Yu-rong.Dynamic Simulation of Chilled Water Storage Air-conditioning System in Fanhai Urban Square 1~t Phase Commercial Construction in Wuhan[J].Refrigeration Air Conditioning & Electric Power Machinery,2013(6):74-79.
Authors:YE Sheng  ZHANG Yin-an  SHI San-ping  ZHANG Ya-nan  GUO Sheng-zhen  MAO Yu-rong
Affiliation:1. Hangzhou Huadianhuayuan Enviromental Engilwering Co., Ltd, Hangzhou 310000, China; 2. Central south Architectural Design Institute, Wuhan 430000, China;3. Hangzhou Electric Institute of Energy environment Co., Ltd, Hangzhou 310000, China)
Abstract:To shift the peak load of the power grid, improve its operating security and decrease the cost of the user, as well as meet the project requirements of LEED clause, time-dependent electricity price, fireflghting tank and a storage air-conditioning system are used in Fanhai city plaza of Wuhan (phase I). The notable feature of this project is the commercial-integrated firefighting tank, which has large storage volume( 1600 m3) and deep water level (8 m). A supporting girder is set up in the middle of the tank. And the influence of supporting girder on thermoeline has been studied by using dynamic simulation method.
Keywords:chilled water storage  thermocline  dynamic simulation