首页 | 本学科首页   官方微博 | 高级检索  
     

220kV线路重复故障时重合闸拒动原因分析及防范措施
引用本文:谭子健. 220kV线路重复故障时重合闸拒动原因分析及防范措施[J]. 广西电力, 2012, 0(2): 71-72,76
作者姓名:谭子健
作者单位:广东电网公司
摘    要:为了提高220 kV及以上输电线路重复故障时重合闸的成功率,通过分析某220 kV线路重合闸不成功的原因及所暴露的问题,采用改变保护装置充电时间、配用一次储能可多次分合的操作机构、合理选择重合闸方式等措施可提高线路重合闸成功率。对避免雷击频繁地区重要线路中断供电有现实指导意义。

关 键 词:继电保护装置  雷击  重合闸

Analysis of and Treatment of Recloser Failure of 220 kV Transmission Line in Multiple Faults
TAN Zi-jian. Analysis of and Treatment of Recloser Failure of 220 kV Transmission Line in Multiple Faults[J]. Guangxi Electric Power, 2012, 0(2): 71-72,76
Authors:TAN Zi-jian
Affiliation:TAN Zi-jian(Guangdong Power Grid Corporation,Guangdong 510600,China)
Abstract:In order to increase the success rate of recloser of 220 kV and above voltage level transmission lines in multiple faults,by analyzing reasons of the recloser failure of a certain 220 kV transmission line and exposed problems,measures to increase the success rate of recloser are found such as changing the charging time of protection equipment,using operating mechanism which has multiple operations with one energy store operation,choosing reasonable reclosing mode and so on,which have practical guide significance for avoiding the power off of important lines in areas with high lightning density.
Keywords:relay protection equipment  lightning strike  recloser
本文献已被 CNKI 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号