影响750kV隔离开关正常操作的因素分析
引用本文:周广伟.影响750kV隔离开关正常操作的因素分析[J].宁夏电力,2013(5):12-15.
作者姓名:周广伟
作者单位:国网宁夏电力公司检修公司,宁夏银川750011
摘    要:针对750kV隔离开关操作存在的问题,从干扰电压的产生及隔离开关位置不易观测等影响因素加以分析,提出了改进的措施。改造结果表明:隔离开关电机二次回路中采用屏蔽电缆,有效地减少了干扰电压,避免了隔离开关分/合闸时因电机电源跳闸引起长时间扯弧而损坏设备的情况发生,保证了电网的安全可靠运行。

关 键 词:750  kV隔离开关  干扰电压  位置指示

Influencing factors analysis of smooth operation for 750 kV isolating switch
ZHOU Guangwei.Influencing factors analysis of smooth operation for 750 kV isolating switch[J].Ningxia Electric Power,2013(5):12-15.
Authors:ZHOU Guangwei
Affiliation:ZHOU Guangwei (Maintenance Filiale of State Grid Ningxia Electric Power Co., Yinchuan Ningxia 750011, China)
Abstract:Aiming at the problems of 750 kV isolating switch operation, analyzes the the influencing factors such as interference voltage and the isolating switch position, puts forward improving mea- sures. The result shows that using shielded cable in secondary loop of electric motor of disconnector, reduces effectively the interference voltage, avoids striking of arc long time when switch off/on of iso- lating switch and ensures power grid operation on the safe side.
Keywords:750 kV isolating switch  interference voltage  position indication