首页 | 本学科首页   官方微博 | 高级检索  
     


Power differential based wide area protection
Authors:F. Namdari  S. Jamali  P.A. Crossley
Affiliation:1. Centre of Excellence for Power Systems, Automation, and Operation, Department of Electrical Engineering, Iran University of Science and Technology, Tehran 16846_13114, Iran;2. School of Electrical & Electronic Engineering, University of Manchester, M60 1QD, Manchester, UK
Abstract:Current differential based wide area protection (WAP) has recently been proposed as a technique to increase the reliability of protection systems. It increases system stability and can prevent large contingencies such as cascading outages and blackouts. This paper describes how power differential protection (PDP) can be used within a WAP and shows that the algorithm operates correctly for all types of system faults whilst preventing unwanted tripping, even if the data has been distorted by CT saturation or by data mismatches caused by delays in the WAP data collection system. The PDP algorithm has been simulated and tested on an Iranian 400 kV transmission line under different fault and system operating conditions. The proposed operating logic and the PDP algorithm have also been evaluated using simulation studies based on the Northern Ireland Electricity (NIE) 275 kV network. The results presented illustrate the validity of the proposed protection.
Keywords:Wide area protection   Power differential algorithm   Current differential relaying   Transmission networks
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏