首页 | 本学科首页   官方微博 | 高级检索  
     


Experimental investigation of adsorption chiller for Micro-scale BCHP system application
Authors:Y Huangfu  JY WuRZ Wang  ZZ Xia
Affiliation:Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, Shanghai 200030, China
Abstract:Building cooling, heating and power (BCHP), is an attracting cogeneration system for its economic and environmental friendly qualities. Therefore, it is meaningful to develop Micro-scale BCHP (MBCHP) system based on adsorption chiller and internal combustion gas engine for the use of residential and light commercial buildings. To guide the optimum matching and operation of adsorption chiller in MBCHP system correctly, this paper deals with the performance of adsorption chiller under varying heating conditions. Experimental results show that the value of COP is high in the operation mode of varying hot water inlet temperature with mass recovery in no heating pattern (VTNH). With the hot water inlet temperature of 65 °C, the value of COP is as high as 0.40 in VTNH mode. Under electricity output conditions from 6.0 to 8.3 kW in MBCHP system, VTNH mode is especially preferred when cooling demand is with priority.
Keywords:BCHP  building cooling heating and power  DES  distributed energy system  MBCHP  Micro-scale building cooling heating and power  temp  temperature  VFH  varying hot water flow rate with mass recovery in heating pattern  VTH  varying hot water inlet temperature with mass recovery in heating pattern  VTNH  varying hot water inlet temperature with mass recovery in no heating pattern