首页 | 本学科首页   官方微博 | 高级检索  
     


Effects of utilizing seawater as a cooling source system in a commercial complex
Authors:Young-hak Song  Yasunori Akashi  Jurng-Jae Yee
Affiliation:1. Faculty of Human-Environment Studies, Kyushu University, Hakozaki 6-10-1, Higashi-ku, Fukuoka 812-8581, Japan;2. Faculty of Architectural Design & Engineering, Dong-A University, 840 Hadan 2-dong, Saha-gu, Busan 604-714, Republic of Korea
Abstract:This paper treats energy and cost performance of a cooling source system with indirect seawater utilization for air conditioning in a commercial complex. Seawater utilization has merits as a cooling source, because seawater temperature is lower than outdoor air in summer and it is cost effective because there is no water monetary cost. Actual operating data has been measured for about 2 years and the chiller and system co-efficient of performance (COP) have indicated about 4.77 and 2.93, respectively, even in summer season and the mean efficiency of the thermal storage system was about 89.9% taking into account heat loss of pumps. In addition, we have constructed simulation models for cooling tower systems, air cooling chiller systems and direct seawater utilization systems then compared them to this system. The electric power consumption of the indirect seawater utilization system was almost the same as the other systems except the air cooling chiller system, because using lower seawater temperature made the chiller efficiency higher. In conclusion, our results showed the indirect seawater utilization system was able to improve the system COP compared to air cooling chiller system, and cancel water consumption compared with the cooling tower system, and cut down an initial and maintenance costs compared with the direct seawater utilization system.
Keywords:Seawater utilization  Cooling source system  Measurement  Model-based simulation  Cost performance
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号