Islanding detection of grid connected distributed generators using TLS-ESPRIT |
| |
Authors: | H.H. Zeineldin T. Abdel-GalilE.F. El-Saadany M.M.A. Salama |
| |
Affiliation: | Department of Electrical and Computer Engineering, University of Waterloo, Waterloo, Ont., Canada N2L 3G1 |
| |
Abstract: | A critical protection requirement for grid connected distributed generators (DG) is anti-islanding protection. In this paper, a new islanding detection method is proposed based on monitoring the generator's frequency. Two new features, the frequency of oscillation and the damping factor of the generator's frequency output waveform, are extracted using the total least square-estimation of signal parameters via rotational invariance techniques (TLS-ESPRIT) algorithm. The proposed method has been tested under various scenarios such as load change, short circuit, and capacitor switching. |
| |
Keywords: | DG, distributed generation TLS-ESPRIT, total least square-estimation of signal parameters via rotational invariance techniques NDZ, non-detective zone AFD, active frequency drift SMFS, slip mode frequency shift THD, total harmonic distortion FFT, fast Fourier transform OVP/UVP, over/under voltage OFP/UFP, over/under frequency |